Satec PM175 Manual User Manual Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 168
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
Chapter 3 Display Operations
Series PM175 Powermeters
49
To exit the menu, press ESC.
The following table lists available setpoint options. For a list of
available setpoint triggers and actions, see Using Control
Setpoints in Chapter 4.
Label
Parameter
Options
Description
LGC.2-
LGC.4
Logical operator
OR, AND
Combines setpoint triggers in a
logical expression
TrG.1-TrG.4
Trigger
parameter #1-
#4
See
Appendix C
The analog or digital value that is
used as an argument in a logical
expression
On.1-On.4
Operate limit
The threshold (in primary units) at
which the conditional expression
would be evaluated to true. Not
applicable for digital triggers.
OFF.1-
OFF.4
Release limit
The threshold (in primary units) at
which the conditional expression
would be evaluated to false. Defines
the hysteresis for analog triggers.
Not applicable for digital triggers.
Act.1-Act.4
Setpoint action
#1-#4
See
Appendix C
The action performed when the
setpoint expression is evaluated to
true (the setpoint is in operated
state)
On d
Operate delay
0-999.9 sec
The time delay before operation
when the operate conditions are
fulfilled
OFF d
Release delay
0-999.9 sec
The time delay before release when
the release conditions are fulfilled
Analog Inputs Setup
This entry appears only if the meter is ordered with optional
analog inputs. For more information on configuring analog
inputs in your meter, see Programming Analog Inputs in
Chapter 4.
To enter the menu, select the “A.In.1” or “A.In.2” entry from the
main menu for the AI1 and AI2 inputs respectively, and press
the ENTER button.
To change the analog input options:
1. Use the UP and DOWN arrow buttons to scroll to the
desired parameter.
2. Press the SELECT button to activate the lower window.
3. Use the UP and DOWN arrow buttons to adjust the
parameter value.
4. Press ENTER to confirm the new parameter setting, or
press ESC to discard changes.
5. You are returned to the middle window to select another
parameter, or store your new settings and exit the menu.
To store new settings and exit the menu:
1. When the middle window is highlighted, press the ENTER
button.
2. You return to the Main menu.
To exit the menu without saving your changes, press ESC.
The following table lists available analog input options.
SEtP
rEL.1
Act.1
SP.1
180
OFF.2
A.In.1
ESC
A.In.1
0
Lo
A.In.1
230
Hi
A.In.1
1
dEc.P
Page view 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 167 168

Comments to this Manuals

No comments