Satec PM175 Manual User Manual Page 142

  • Download
  • Add to my manuals
  • Print
  • Page
    / 168
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 141
Appendix A Technical Specifications
142
Series PM175 Powermeters
Communication Ports
COM1 (Optional modules)
Serial EIA RS-232 optically isolated port
Isolation: 2,000 V RMS
Connector type: DB9 female.
Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).
RS-422/RS-485 optically isolated port
Isolation: 2,000 V RMS
Connector type: DB9 female.
Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).
Ethernet Port
Transformer-isolated 10/100BaseT Ethernet port.
Connector type: RJ45 modular.
Supported protocols: Modbus/TCP on Port 502, DNP3/TCP on
Port 20000 (with firmware V25.2.01 and later).
Number of simultaneous connections: 4 (4 Modbus/TCP or 2
Modbus/TCP + 2 DNP3/TCP).
Dial-up Modem
Transformer-isolated internal 56K modem.
Connector type: RJ11.
Supported protocols: Modbus RTU and Modbus ASCII.
COM2
RS-422/RS-485 optically isolated port
Isolation: 2,000 V RMS
Connector type: removable, 5 pins.
Wire size: up to 14 AWG (up to 1.5 mm
2
).
Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).
Real-time Clock
Accuracy: typical error 30 seconds per month
@
25
C
Log Memory
Onboard memory with battery backup: 1 Mbytes.
Display Module
Display: high-brightness seven-segment digital LEDs, two 4-
digit + one 6-digit windows
Keypad: 6 push buttons
Communication: EIA RS-485 port with 12V supply voltage
Connector type: DB15, 15 pins
Wires size: up to 14 AWG (up to 1.5 mm
2
)
Distance: up to 1000 m (3200 feet)
Page view 141