Chapter 3 Display Operations
Series PM175 Powermeters
53
Label
Parameter
Options
Description
Lo
Zero scale
Low engineering scale (in primary
units) for the analog output
corresponding to a lowest (zero)
output current (0 or 4 mA)
Hi
Full scale
High engineering scale (in primary
units) for the analog output
corresponding to a highest output
current (1 or 20 mA)
Analog expander outputs are not operational until you globally
enable the analog expander option in your meter through the Device
Options menu.
Timers Setup
The PM175 is provided with four interval timers. When
enabled, a timer generates periodic events in predefined
intervals that can trigger setpoints to produce periodic actions
like periodic data trending. To enter the menu, select the “t-r”
entry from the main menu and press the ENTER button.
Use the UP and DOWN arrow buttons to scroll to the desired
timer.
To change the time period for the timer:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to enter the desired
interval value in seconds. Intervals from 1 to 9999
seconds are allowed. Resetting the interval to 0 disables
the timer.
3. Press ENTER to confirm your changes and to save the
new settings, or press ESC to discard changes.
4. You are returned to the middle window to select another
timer or exit the menu.
To exit the menu, press ESC.
Display Setup
This menu allows you to configure options for the meter
display, and view display and device firmware versions. To
enter the menu, select the “diSP” entry from the main menu
and press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the
desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the
desired option.
3. Press ENTER to confirm the changes and to save your
new setting, or press ESC to discard changes.
To exit the menu, press ESC.
The following table lists available options.
t-r
0
t-r.1
diSP
1.0
UPdt
Page view 52