Chapter 4 PAS Application Software
92
Series PM175 Powermeters
3. Select the maximum number of records you want to be
recorded in the file.
The number of records in the waveform log file needed to
store one waveform event (series) is defined as follows:
Number of Records per Series = Sampling Rate (Samples
per Cycle) x Number of Cycles per Event / 512
The total number of records you must allocate to store the
required number of events (series) is defined as follows:
Number of Records = Number of Records per Series x
Number of Series
For example, if you want to record a 64-cycle waveform
sampled at a rate of 32 samples per cycle, the number of
records required for one waveform series would be:
Number of Records per Series = (32 x 64)/512 = 4.
If you want to allocate space sufficient to store 20
waveform events (series), you should set up the
waveform log file for 4 x 20 = 80 records.
4. Click OK, and send your setup to the meter or save to the
database.
5. Click “Setup Recorder”, or click on the “Waveform
Recorder” tab.
The following table lists available waveform options.
Option
Format/Range
Description
Samples per Cycle
32, 64, 128
Waveform sampling rate
Cycles per Series
16-2560 (32 samples/cycle),
8-1280 (64 samples/cycle),
4-640 (128 samples/cycle)
Defines the total duration of the
waveform per event/series
Before Cycles
1-20
Defines the number of cycles to be
recorded prior to event
Num. of Channels
1-6
The number of the simultaneously
recorded channels
6. Select the sampling rate for waveforms.