Appendix E EN50160 Statistics Log Files
Appendix E EN50160 Statistics Log Files
The following table lists the EN50160 evaluation parameters
recorded by the meter in the EN50160 statistics data log files.
The second column shows data abbreviations used in the PAS
data log reports. Data log files’ sections are highlighted by a
bold font.
EN50160 Compliance Statistics Log (Data Log #9)
Number of non-valid 10-sec intervals
Number of valid 10-sec intervals
Number of incidents ±1%, N1
Number of incidents +4%/-6%, N2
EN50160 compliance ratio, N1/N
EN50160 compliance ratio, N2/N
Supply Voltage Variations
Number of non-valid 10-min intervals
Number of valid 10-min intervals
Number of polyphase incidents ±10%, N1
Number of polyphase incidents +10/-15%, N2
EN50160 compliance ratio, N1/N
EN50160 compliance ratio, N2/N
Number of incidents ±10% on phase V1
Minimum voltage on phase V1
Maximum voltage on phase V1
Number of incidents ±10% on phase V2
Minimum voltage on phase V2
Maximum voltage on phase V2
Number of incidents ±10% on phase V3
Minimum voltage on phase V3
Maximum voltage on phase V3
Number of polyphase incidents
Number of incidents on phase V1
Maximum voltage variation on phase V1, dV/Un%
Number of incidents on phase V2
Maximum voltage variation on phase V2, dV/Un%
Number of incidents on phase V3
Maximum voltage variation on phase V3, dV/Un%
Number of non-valid 10-min intervals
Number of valid 10-min intervals
Number of polyphase incidents Plt >1%, N1
EN50160 compliance ratio, N1/N
Number of incidents Plt > 1% on phase V1
Number of incidents Plt > 1% on phase V2
Number of incidents Plt > 1% on phase V3
Voltage Dips (indicative statistics)
Number of polyphase incidents u<90%/t<100ms
Number of polyphase incidents u<85%/t<100ms
Number of polyphase incidents u<70%/t<100ms
Number of polyphase incidents u<40%/t<100ms
Number of polyphase incidents u<90%/t<500ms
Number of polyphase incidents u<85%/t<500ms
Number of polyphase incidents u<70%/t<500ms
Number of polyphase incidents u<40%/t<500ms
Comments to this Manuals