Satec PM175 Manual User Manual Page 163

  • Download
  • Add to my manuals
  • Print
  • Page
    / 168
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 162
Appendix E EN50160 Statistics Log Files
Series PM175 Powermeters
163
Appendix E EN50160 Statistics Log Files
The following table lists the EN50160 evaluation parameters
recorded by the meter in the EN50160 statistics data log files.
The second column shows data abbreviations used in the PAS
data log reports. Data log files’ sections are highlighted by a
bold font.
EN50160 Compliance Statistics Log (Data Log #9)
Field No.
Designation
Description
Power Frequency
1
Nnv
Number of non-valid 10-sec intervals
2
N
Number of valid 10-sec intervals
3
N1
Number of incidents ±1%, N1
4
N2
Number of incidents +4%/-6%, N2
5
N1/N, %
EN50160 compliance ratio, N1/N
6
N2/N, %
EN50160 compliance ratio, N2/N
7
Freq Min
Minimum frequency
8
Freq Max
Maximum frequency
Supply Voltage Variations
1
Nnv
Number of non-valid 10-min intervals
2
N
Number of valid 10-min intervals
3
N1
Number of polyphase incidents ±10%, N1
4
N2
Number of polyphase incidents +10/-15%, N2
5
N1/N, %
EN50160 compliance ratio, N1/N
6
N2/N, %
EN50160 compliance ratio, N2/N
7
V1 N1
Number of incidents ±10% on phase V1
8
V1 Min
Minimum voltage on phase V1
9
V1 Max
Maximum voltage on phase V1
10
V2 N1
Number of incidents ±10% on phase V2
11
V2 Min
Minimum voltage on phase V2
12
V2 Max
Maximum voltage on phase V2
13
V3 N1
Number of incidents ±10% on phase V3
14
V3 Min
Minimum voltage on phase V3
15
V3 Max
Maximum voltage on phase V3
Rapid Voltage Changes
1
N1
Number of polyphase incidents
2
V1 N1
Number of incidents on phase V1
3
V1 dV%
Maximum voltage variation on phase V1, dV/Un%
4
V2 N1
Number of incidents on phase V2
5
V2 dV%
Maximum voltage variation on phase V2, dV/Un%
6
V3 N1
Number of incidents on phase V3
7
V3 dV%
Maximum voltage variation on phase V3, dV/Un%
Flicker
1
Nnv
Number of non-valid 10-min intervals
2
N
Number of valid 10-min intervals
3
N1
Number of polyphase incidents Plt >1%, N1
4
N1/N, %
EN50160 compliance ratio, N1/N
5
V1 N1
Number of incidents Plt > 1% on phase V1
6
V1 Plt Max
Maximum Plt on phase V2
7
V2 N1
Number of incidents Plt > 1% on phase V2
8
V2 Plt Max
Maximum Plt on phase V2
9
V3 N1
Number of incidents Plt > 1% on phase V3
10
V3 Plt Max
Maximum Plt on phase V3
Voltage Dips (indicative statistics)
1
N11 90%/100ms
Number of polyphase incidents u<90%/t<100ms
2
N12 85%/100ms
Number of polyphase incidents u<85%/t<100ms
3
N13 70%/100ms
Number of polyphase incidents u<70%/t<100ms
4
N14 40%/100ms
Number of polyphase incidents u<40%/t<100ms
5
N11 90%/500ms
Number of polyphase incidents u<90%/t<500ms
6
N12 85%/500ms
Number of polyphase incidents u<85%/t<500ms
7
N13 70%/500ms
Number of polyphase incidents u<70%/t<500ms
8
N14 40%/500ms
Number of polyphase incidents u<40%/t<500ms
Page view 162

Comments to this Manuals

No comments