Appendix E EN50160 Statistics Log Files
164
Series PM175 Powermeters
Field No.
Designation
Description
9
N11 90%/1s
Number of polyphase incidents u<90%/t<1s
10
N12 85%/1s
Number of polyphase incidents u<85%/t<1s
11
N13 70%/1s
Number of polyphase incidents u<70%/t<1s
12
N14 40%/1s
Number of polyphase incidents u<40%/t<1s
13
N11 90%/3s
Number of polyphase incidents u<90%/t<3s
14
N12 85%/3s
Number of polyphase incidents u<85%/t<3s
15
N13 70%/3s
Number of polyphase incidents u<70%/t<3s
16
N14 40%/3s
Number of polyphase incidents u<40%/t<3s
17
N11 90%/20s
Number of polyphase incidents u<90%/t<20s
18
N12 85%/20s
Number of polyphase incidents u<85%/t<20s
19
N13 70%/20s
Number of polyphase incidents u<70%/t<20s
20
N14 40%/20s
Number of polyphase incidents u<40%/t<20s
21
N11 90%/60s
Number of polyphase incidents u<90%/t<60s
22
N12 85%/60s
Number of polyphase incidents u<85%/t<60s
23
N13 70%/60s
Number of polyphase incidents u<70%/t<60s
24
N14 40%/60s
Number of polyphase incidents u<40%/t<60s
25
N11 90%/180s
Number of polyphase incidents u<90%/t<180s
26
N12 85%/180s
Number of polyphase incidents u<85%/t<180s
27
N13 70%/180s
Number of polyphase incidents u<70%/t<180s
28
N14 40%/180s
Number of polyphase incidents u<40%/t<180s
29
V1 N1
Total number of incidents on phase V1
30
V1 Min
Minimum residual voltage on phase V1
31
V2 N1
Total number of incidents on phase V2
32
V2 Min
Minimum residual voltage on phase V2
33
V3 N1
Total number of incidents on phase V3
34
V3 Min
Minimum residual voltage on phase V3
Voltage Interruptions (indicative statistics)
1
N1 1s
Number of polyphase incidents t<1s
2
N2 180s
Number of polyphase incidents t<180s
3
N3 >180s
Number of polyphase incidents t>180s
4
V1 Min
Minimum residual voltage on phase V1
5
V2 Min
Minimum residual voltage on phase V2
6
V3 Min
Minimum residual voltage on phase V3
Temporary Overvoltages (indicative statistics)
1
N11 110%/1s
Number of polyphase incidents u>110%/t<1s
2
N12 120%/1s
Number of polyphase incidents u>120%/t<1s
3
N13 140%/1s
Number of polyphase incidents u>140%/t<1s
4
N14 160%/1s
Number of polyphase incidents u>160%/t<1s
5
N15 200%/1s
Number of polyphase incidents u>200%/t<1s
6
N21 110%/60s
Number of polyphase incidents u>110%/t<60s
7
N22 120%/60s
Number of polyphase incidents u>120%/t<60s
8
N23 140%/60s
Number of polyphase incidents u>140%/t<60s
9
N24 160%/60s
Number of polyphase incidents u>160%/t<60s
10
N25 200%/60s
Number of polyphase incidents u>200%/t<60s
11
N31 110%/>60s
Number of polyphase incidents u>110%/t>60s
12
N32 120%/>60s
Number of polyphase incidents u>120%/t>60s
13
N33 140%/>60s
Number of polyphase incidents u>140%/t>60s
14
N34 160%/>60s
Number of polyphase incidents u>160%/t>60s
15
N35 200%/>60s
Number of polyphase incidents u>200%/t>60s
16
V1 N1
Total number of incidents on phase V1
17
V1 Max
Maximum voltage magnitude on phase V1
18
V2 N1
Total number of incidents on phase V2
19
V2 Max
Maximum voltage magnitude on phase V2
20
V3 N1
Total number of incidents on phase V3
21
V3 Max
Maximum voltage magnitude on phase V3
Transient Overvoltages (indicative statistics)
1
N1 110%
Number of polyphase incidents u>120%
2
N2 150%
Number of polyphase incidents u>150%
3
N3 200%
Number of polyphase incidents u>200%
4
N4 250%
Number of polyphase incidents u>250%
5
N5 300%
Number of polyphase incidents u>300%
6
V1 N1 110%
Number of incidents u>120% on phase V1
7
V1 N2 150%
Number of incidents u>150% on phase V1
8
V1 N3 200%
Number of incidents u>200% on phase V1
9
V1 N4 250%
Number of incidents u>250% on phase V1
10
V1 N5 300%
Number of incidents u>300% on phase V1
Page view 163